Dallas, Texas
Building construction codes effective March 1, 2017 or as noted otherwise. Click the links below to download the PDF files.
CHAPTER 16: 2015 International Fire Code, including Appendix J, with Dallas Amendments (effective October 1, 2016)https://dallascityhall.com/departments/sustainabledevelopment/buildinginspection/DCH%20documents/pdf/BI_Ord30135_IFC2015.pdf
CHAPTER 53: 2015 International Building Code with Dallas Amendments https://dallascityhall.com/departments/sustainabledevelopment/buildinginspection/DCH%20documents/pdf/BI_2015_IBC_Amendments_01-25-2017.pdf
Section 1104 – Means of Egress Requirements
1104.16.5 Materials and strength.Components of fire escape stairways shall be constructed of noncombustible materials. Fire escape stairways and balconies shall support the dead load plus a live load of not less than 100 pounds per square foot (4.78 kN/m2) . Fire escape stairways and balconies shall be provided with a top and intermediate handrail on each side.
1104.16.5.1 Examination. Fire escape stairways and balconies shall be examined for structural adequacy and safety in accordance with Section II 04.16.5 by a registered design professional or others acceptable to the fire code official every 5 years, or as required by the fire code official. An inspection report shall be submitted to the fire code official after such examination.
1104.16.6 Termination.The lowest balcony shall not be more than 18 feet (5486 mm) Frf>m the ground. Fire escape stairways shall extend to the ground or be provided with counterbalanced stairs reaching the ground. Exception: For fire escape stairways serving 10 or fewer occupants, an approved fire escape ladder is allowed to serve as the termination.
1104.16.7 Maintenance.Fire escape stairways shall be kept clear and unobstructed at all times and shall be maintained in good working order.
Section 105 – Permits
[A] 105.1 General. Permits shall be in accordance with Sections 105.1.1 through 105.7.18.
[A] 105.1.4 Emergency repairs. Where equipment replacement and repairs must be performed in an emergency situation, the permit application shall be submitted within the next working business day to the fire code official.
[A] 105.1.5 Repairs. Application or notice to the fire code official is not required for ordinary repairs to structures,equipment or systems. Such repairs shall not include thecutting away of any wall, partition or portion thereof, theremoval or change of any required means of egress, or rearrangement of parts of a structure affecting the egress requirements; nor shall any repairs include addition to, alteration of replacement or relocation of any standpipe, fire protection water supply, automatic sprinkler system, fire alarm system or other work affecting fire protection or life safety.
Section 106 – Inspections
[A] 106.1 Inspection authority. The fire code official is authorized to enter and examine any building, structure, marine vessel, vehicle or premises in accordance with Section 104.3 for the purpose of enforcing this code.
[A] 106.2 Inspections. The fire code official is authorized to conduct such inspections as are deemed necessary to determine the extent of compliance with the provisions of this code and to approve reports of inspection by approved agencies or individuals. Reports of such inspections shall be prepared and submitted in writing for review and approval. Inspection reports shall be certified by a responsible officer of such approved agency or by the responsible individual. The fire code official is authorized to engage such expert opinion as deemed necessary to report upon unusual, detailed or complex technical issues subject to the approval of the governing body.
Section 107 – Maintenance
[A] 107.1 Maintenance of safeguards. Where any device, equipment, system, condition, arrangement, level of protection, or any other feature is required for compliance with the provisions of this code, or otherwise installed, such device, equipment, system, condition, arrangement, level of protection, or other feature shall thereafter be continuously maintained in accordance with this code and applicable referenced standards.
[A] 107.2 Testing and operation. Equipment requiring periodic testing or operation to ensure maintenance shall be tested or operated as specified in this code.
[A] 107.2.1 Re-inspection and testing. Where any work or installation does not pass an initial test or inspection, the necessary corrections shall be made so as to achieve compliance with this code. The work or installation shall then be resubmitted to the fire code official for inspection and testing.
Section 110 – Unsafe Buildings
[A] 110.1 General. If during the inspection of a premises, a building or structure, or any building system, in whole or in part, constitutes a clear and inimical threat to human life, safety or health, the fire code official shall issue such notice or orders to remove or remedy the conditions as shall be deemed necessary in accordance with this section, and shall refer the building to the building department for any repairs, alterations, remodeling, removing or demolition required.
[A] 110.1.1 Unsafe conditions. Structures or existing equipment that are or hereafter become unsafe or deficient because of inadequate means of egress or which constitute a fire hazard, or are otherwise dangerous to human life or the public welfare, or which involve illegal or improper occupancy or inadequate maintenance, shall be deemed an unsafe condition. A vacant structure that is not secured against unauthorized entry as required by Section 311 shall be deemed unsafe.
[A] 110.1.2 Structural hazards. Where an apparent structural hazard is caused by the faulty installation, operation or malfunction of any of the items or devices governed by this code, the fire code official shall immediately notify the building code official in accordance with Section 110.1.
[A] 110.2 Evacuation. The fire code official or the fire department official in charge of an incident shall be authorized to order the immediate evacuation of any occupied building deemed unsafe where such building has hazardous conditions that present imminent danger to building occupants. Persons so notified shall immediately leave the structure or premises and shall not enter or re-enter until authorized to do so by the fire code official or the fire department official in charge of the incident.
[A] 110.3 Summary abatement. Where conditions exist that are deemed hazardous to life and property, the fire code officialor fire department official in charge of the incident is authorized to abate summarily such hazardous conditions that are in violation of this code.
[A] 110.4 Abatement. The owner, the owner’s authorized agent, operator or occupant of a building or premises deemed unsafe by the fire code official shall abate or cause to be abated or corrected such unsafe conditions either by repair, rehabilitation, demolition or other approved corrective action.
Source:ICC, 2015 International Fire Code w/ Dallas Amendments
Sec. 791.016. PAINTING AND MAINTENANCE REQUIREMENTS. (a) A fire escape constructed of iron or steel must be painted with at least two coats of good metallic paint when erected. The fire escape must be repainted at least every two years or more frequently if necessary to preserve the fire escape from rust or climatic influences.
(b) The slideway of a straight or spiral chute fire escape must be thoroughly cleaned and painted at least once each year.
Acts 1989, 71st Leg., ch. 678, Sec. 1, eff. Sept. 1, 1989.
Send us photos of your fire escape by email: info@FireEscapesDallas.com
or click here to submit via an online form
NATIONAL CODES:
2015 IFC 1104.16.5.1 Fire escape stairs must be examined every 5 years ,by design professional or others acceptable and inspection report must be submitted to the fire code official.
IFC 2015 1104.16 PDF copy of actual code
IBC 1001.3.3 All fire escapes shall be examined and/or tested and certified every five years by a design professional or others acceptable who will then submit an affidavit city official.
NFPA LIFE SAFETY CODE 101 7.2.8.6.2 The Authority Having Jurisdiction (AHJ) shall approve any fire escape by Load Test or other evidence of strength (Certification).
OSHA 1910.37 Exit routes must be maintained during construction, repairs, alterations or provide alternative egress with equivalent level of safety. (permit issued if egress is certified or with egress scaffolding)
FIVE STEPS to Certify a Fire Escape:
- Schedule a pre load test evaluation by a design professional or others acceptable by City Official – AHJ (Authority Having Jurisdiction)
- Said professional will confirm with City Official if there are any other requirements other than load testing or other evidence of strength and if City Official wants to witness initial evaluation
- Submit evaluation report to owner/agent and a copy to the City Official as per code
- Issue certification, if passed, done by load test or other evidence of strength to City Official or, if failed, owner/agent and city official to confirm next steps (ex. engineer oversight, permits or other conditions)
- Please contact your local City Official (AHJ) with any questions about the above steps